Backflow assembly test: 9449 Pine Knoll Ln

Approved

Filed Oct 5, 2024 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 5, 2024
Assembly type
RP
Serial number
A176515
Size
3/4
Test gauge serial
G-8287
Gauge calibration date
Jan 6, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-10-01325
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9449 Pine Knoll Ln
Owner: Morgan Lindqvist
Parcel 075-10-01325