Backflow assembly test: Station Taqueria

Approved

Filed Apr 18, 2026 by Jamie Vance, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 18, 2026
Assembly type
RP
Serial number
Z826193
Size
1
Test gauge serial
G-4201
Gauge calibration date
Dec 23, 2025
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Vance, current on the service date
  • All required fields present
  • Address matches parcel 075-84-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

214 Hickory Dr
Owner: Ashby Holdings LLC
Parcel 075-84-01034