Back to the backflow review queue

Backflow assembly test: Riverside Diner

Approved

Filed May 16, 2024 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
May 16, 2024
Assembly type
RP
Serial number
W795443
Size
1 1/2
Test gauge serial
G-9833
Gauge calibration date
Aug 31, 2023
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-39-01320
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3400 Old Church Rd
Owner: Marsh Holdings LLC
Parcel 075-39-01320