Back to the backflow review queue
Backflow assembly test: 3418 Quarry Way
ApprovedFiled Jan 18, 2026 by Quinn Stroud, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 18, 2026
- Assembly type
- RP
- Serial number
- B322931
- Size
- 3/4
- Test gauge serial
- G-3475
- Gauge calibration date
- Nov 28, 2025
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Stroud, current on the service date
- All required fields present
- Address matches parcel 075-63-01152
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3418 Quarry Way
Owner: Casey Stroud
Parcel 075-63-01152