Backflow assembly test: 3201 Mill Creek Trl

Approved

Filed Jan 17, 2025 by Morgan Calloway, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 17, 2025
Assembly type
RP
Serial number
W573613
Size
3/4
Test gauge serial
G-9934
Gauge calibration date
May 22, 2024
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-84-01179
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3201 Mill Creek Trl
Owner: Cameron Okafor
Parcel 077-84-01179