Back to the backflow review queue

Backflow assembly test: Crossroads Medical Offices

Approved

Filed Sep 25, 2023 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 25, 2023
Assembly type
DC
Serial number
K594835
Size
4
Test gauge serial
G-4153
Gauge calibration date
Jan 23, 2023
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-57-01173
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6916 Turkey Hill Ln
Owner: Fairley Holdings LLC
Parcel 077-57-01173