Backflow assembly test: 2209 Orchard Trl

Approved

Filed Aug 26, 2026 by Alex Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Aug 26, 2026
Assembly type
PVB
Serial number
B347650
Size
1
Test gauge serial
G-6324
Gauge calibration date
Dec 15, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-30-01295
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.