Backflow assembly test: 6429 Turkey Hill Ln
Sent backFiled Nov 17, 2026 by Casey Lindqvist, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 17, 2026
- Assembly type
- RP
- Serial number
- W395959
- Size
- 1
- Test gauge serial
- G-6387
- Gauge calibration date
- Apr 17, 2026
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Lindqvist, current on the service date
- All required fields present
- Address matches parcel 077-65-01171
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
6429 Turkey Hill Ln
Owner: Rowan Calloway
Parcel 077-65-01171