Backflow assembly test: 4048 Mill Creek Ct

Approved

Filed Jan 29, 2025 by Casey Lindqvist, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 29, 2025
Assembly type
DC
Serial number
Z604724
Size
3/4
Test gauge serial
G-1199
Gauge calibration date
Jul 15, 2024
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 077-25-01353
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4048 Mill Creek Ct
Owner: Reese Okafor
Parcel 077-25-01353