Backflow assembly test: 4886 Mill Creek Rd

Approved

Filed Jun 2, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 2, 2025
Assembly type
RP
Serial number
K770624
Size
1
Test gauge serial
G-1114
Gauge calibration date
Mar 10, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.4 psid
Relief valve opened at
2.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-50-01285
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4886 Mill Creek Rd
Owner: Taylor Kessler
Parcel 077-50-01285