Backflow assembly test: Golden Diner

Approved

Filed Jun 17, 2026 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 17, 2026
Assembly type
RP
Serial number
K475063
Size
1
Test gauge serial
G-2307
Gauge calibration date
Dec 28, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-32-01108
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.