Back to the backflow review queue

Backflow assembly test: 1396 Orchard Dr

Approved

Filed May 28, 2025 by Alex Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
May 28, 2025
Assembly type
RP
Serial number
B300276
Size
1
Test gauge serial
G-9760
Gauge calibration date
Dec 30, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-17-01261
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1396 Orchard Dr
Owner: Logan Whitcomb
Parcel 077-17-01261