Back to the backflow review queue

Backflow assembly test: Crossroads Brewing Co

Approved

Filed Apr 16, 2025 by Alex Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Apr 16, 2025
Assembly type
RP
Serial number
B115340
Size
2
Test gauge serial
G-2093
Gauge calibration date
Mar 15, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-85-01040
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5163 Pine Knoll Dr
Owner: Stroud Holdings LLC
Parcel 077-85-01040