Backflow assembly test: 6138 Old Church Ln
ApprovedFiled Nov 12, 2024 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 12, 2024
- Assembly type
- PVB
- Serial number
- Z269249
- Size
- 3/4
- Test gauge serial
- G-9031
- Gauge calibration date
- Sep 10, 2024
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Hollins, current on the service date
- All required fields present
- Address matches parcel 077-46-01190
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.