Back to the backflow review queue

Backflow assembly test: 8032 Spring Branch Rd

Approved

Filed Apr 9, 2026 by Reese Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 9, 2026
Assembly type
RP
Serial number
B138245
Size
3/4
Test gauge serial
G-4701
Gauge calibration date
Oct 29, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 079-30-01078
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8032 Spring Branch Rd
Owner: Parker Ashby
Parcel 079-30-01078