Back to the backflow review queue

Backflow assembly test: 315 Pine Knoll Ln

Approved

Filed Oct 19, 2025 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 19, 2025
Assembly type
PVB
Serial number
Z534316
Size
1
Test gauge serial
G-4435
Gauge calibration date
Mar 11, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 079-27-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

315 Pine Knoll Ln
Owner: Logan Calloway
Parcel 079-27-01257