Backflow assembly test: 315 Pine Knoll Ln
ApprovedFiled Oct 19, 2025 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 19, 2025
- Assembly type
- PVB
- Serial number
- Z534316
- Size
- 1
- Test gauge serial
- G-4435
- Gauge calibration date
- Mar 11, 2025
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 079-27-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.