Back to the backflow review queue
Backflow assembly test: Corner Taqueria
ApprovedFiled Jun 16, 2023 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 16, 2023
- Assembly type
- RP
- Serial number
- K738590
- Size
- 1
- Test gauge serial
- G-2371
- Gauge calibration date
- Oct 17, 2022
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Lindqvist, current on the service date
- All required fields present
- Address matches parcel 079-29-01262
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1394 Pine Knoll Ct
Owner: Ellery Holdings LLC
Parcel 079-29-01262