Backflow assembly test: Main Street Elementary School
ApprovedFiled Nov 13, 2026 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 13, 2026
- Assembly type
- RP
- Serial number
- W665014
- Size
- 4
- Test gauge serial
- G-8870
- Gauge calibration date
- Jun 22, 2026
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 079-75-01172
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1057 Laurel Way
Owner: Ellery Holdings LLC
Parcel 079-75-01172