Backflow assembly test: 224 Pine Knoll Trl

Approved

Filed Apr 24, 2025 by Sam Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Apr 24, 2025
Assembly type
RP
Serial number
Z867518
Size
1
Test gauge serial
G-5356
Gauge calibration date
Oct 8, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-69-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.