Backflow assembly test: Station Market
ApprovedFiled Aug 24, 2026 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 24, 2026
- Assembly type
- RP
- Serial number
- A498387
- Size
- 4
- Test gauge serial
- G-3652
- Gauge calibration date
- Nov 16, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 079-60-01118
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
379 Fox Run Ln
Owner: Ashby Holdings LLC
Parcel 079-60-01118