Backflow assembly test: Crossroads Grill

Approved

Filed May 19, 2024 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 19, 2024
Assembly type
RP
Serial number
K756640
Size
2
Test gauge serial
G-1361
Gauge calibration date
Feb 8, 2023
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.2 psid
Relief valve opened at
3.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-10-01112
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4527 Sycamore Trl
Owner: Brandt Holdings LLC
Parcel 079-10-01112