Backflow assembly test: Crossroads Grill
ApprovedFiled Jun 25, 2025 by Parker Okafor, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 25, 2025
- Assembly type
- RP
- Serial number
- K756640
- Size
- 2
- Test gauge serial
- G-2733
- Gauge calibration date
- Jul 20, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-10-01112
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.