Backflow assembly test: 441 Sycamore Way
ApprovedFiled Oct 5, 2023 by Parker Nguyen, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 5, 2023
- Assembly type
- RP
- Serial number
- K222300
- Size
- 1
- Test gauge serial
- G-6916
- Gauge calibration date
- Jul 9, 2023
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 079-14-01147
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.