Backflow assembly test: 6501 Spring Branch Rd

Approved

Filed Aug 1, 2023 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 1, 2023
Assembly type
DC
Serial number
B548926
Size
3/4
Test gauge serial
G-9796
Gauge calibration date
Dec 7, 2022
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-31-01260
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6501 Spring Branch Rd
Owner: Parker Lindqvist
Parcel 079-31-01260