Back to the backflow review queue
Backflow assembly test: 2780 Old Church Rd
ApprovedFiled Sep 9, 2026 by Parker Nguyen, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 9, 2026
- Assembly type
- RP
- Serial number
- Z319209
- Size
- 1
- Test gauge serial
- G-4678
- Gauge calibration date
- Feb 2, 2026
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 079-92-01254
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2780 Old Church Rd
Owner: Parker Brandt
Parcel 079-92-01254