Back to the backflow review queue

Backflow assembly test: 6253 Laurel Ct

Approved

Filed Dec 10, 2024 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 10, 2024
Assembly type
RP
Serial number
W965746
Size
1
Test gauge serial
G-1698
Gauge calibration date
Apr 26, 2024
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-53-01096
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6253 Laurel Ct
Owner: Casey Pruitt
Parcel 079-53-01096