Backflow assembly test: Maple Leaf Diner
ApprovedFiled Sep 16, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 16, 2026
- Assembly type
- RP
- Serial number
- Z771893
- Size
- 1 1/2
- Test gauge serial
- G-5161
- Gauge calibration date
- Jan 5, 2026
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-17-01208
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.