Back to the backflow review queue
Backflow assembly test: 4990 Ridgeview Way
ApprovedFiled Oct 13, 2026 by Sam Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 13, 2026
- Assembly type
- DC
- Serial number
- A240440
- Size
- 1
- Test gauge serial
- G-7004
- Gauge calibration date
- Apr 27, 2026
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-46-01155
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4990 Ridgeview Way
Owner: Jamie Okafor
Parcel 079-46-01155