Backflow assembly test: 7551 Cedar Hollow Ln
ApprovedFiled Feb 27, 2026 by Parker Okafor, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Feb 27, 2026
- Assembly type
- DC
- Serial number
- K854602
- Size
- 1
- Test gauge serial
- G-3689
- Gauge calibration date
- Aug 30, 2025
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-56-01018
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7551 Cedar Hollow Ln
Owner: Blake Kessler
Parcel 079-56-01018