Backflow assembly test: 7517 Ridgeview Rd
ApprovedFiled Nov 3, 2024 by Cameron Lindqvist, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 3, 2024
- Assembly type
- PVB
- Serial number
- Z899774
- Size
- 3/4
- Test gauge serial
- G-2514
- Gauge calibration date
- Jan 30, 2024
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Lindqvist, current on the service date
- All required fields present
- Address matches parcel 079-99-01342
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.