Backflow assembly test: 3915 Sycamore Way
ApprovedFiled Nov 27, 2025 by Parker Okafor, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 27, 2025
- Assembly type
- PVB
- Serial number
- K451241
- Size
- 3/4
- Test gauge serial
- G-2854
- Gauge calibration date
- Jul 19, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-67-01209
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.