Backflow assembly test: 1399 Quarry Ct

Approved

Filed Jun 6, 2026 by Reese Ashby, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 6, 2026
Assembly type
PVB
Serial number
B689820
Size
3/4
Test gauge serial
G-1233
Gauge calibration date
Feb 15, 2026
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ashby, current on the service date
  • All required fields present
  • Address matches parcel 083-95-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1399 Quarry Ct
Owner: Avery Calloway
Parcel 083-95-01153