Backflow assembly test: 4121 Turkey Hill Ln

Approved

Filed Mar 26, 2025 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 26, 2025
Assembly type
DC
Serial number
B185890
Size
1
Test gauge serial
G-6538
Gauge calibration date
Oct 19, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-44-01235
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4121 Turkey Hill Ln
Owner: Shawn Okafor
Parcel 083-44-01235