Back to the backflow review queue

Backflow assembly test: Main Street Animal Hospital

Approved

Filed Nov 20, 2025 by Reese Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 20, 2025
Assembly type
DC
Serial number
Z493652
Size
4
Test gauge serial
G-5577
Gauge calibration date
Jun 11, 2025
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Kessler, current on the service date
  • All required fields present
  • Address matches parcel 083-66-01312
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

425 Old Church Ct
Owner: Marsh Holdings LLC
Parcel 083-66-01312