Back to the backflow review queue

Backflow assembly test: Main Street Diner

Approved

Filed Nov 25, 2025 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 25, 2025
Assembly type
RP
Serial number
A134886
Size
2
Test gauge serial
G-5800
Gauge calibration date
Feb 18, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-41-01044
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

858 Turkey Hill Dr
Owner: Okafor Holdings LLC
Parcel 083-41-01044