Back to the backflow review queue
Backflow assembly test: 3742 Ridgeview Ct
ApprovedFiled Jul 31, 2025 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 31, 2025
- Assembly type
- RP
- Serial number
- B564703
- Size
- 3/4
- Test gauge serial
- G-4145
- Gauge calibration date
- Feb 9, 2025
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Ellery, current on the service date
- All required fields present
- Address matches parcel 083-69-01108
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3742 Ridgeview Ct
Owner: Avery Danner
Parcel 083-69-01108