Back to the backflow review queue

Backflow assembly test: 8805 Old Church Ct

Approved

Filed Dec 28, 2025 by Parker Vance, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Dec 28, 2025
Assembly type
RP
Serial number
K167387
Size
3/4
Test gauge serial
G-3418
Gauge calibration date
May 6, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 083-45-01307
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8805 Old Church Ct
Owner: Quinn Harlow
Parcel 083-45-01307