Backflow assembly test: 7775 Pine Knoll Way
ApprovedFiled Jun 28, 2025 by Casey Ellery, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jun 28, 2025
- Assembly type
- DC
- Serial number
- Z923755
- Size
- 1
- Test gauge serial
- G-3562
- Gauge calibration date
- Jan 1, 2025
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Ellery, current on the service date
- All required fields present
- Address matches parcel 083-83-01129
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7775 Pine Knoll Way
Owner: Shawn Vance
Parcel 083-83-01129