Backflow assembly test: 5874 Ridgeview Rd
Sent backFiled Nov 23, 2026 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- DC
- Serial number
- A509164
- Size
- 3/4
- Test gauge serial
- G-3920
- Gauge calibration date
- Sep 6, 2026
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Ellery, current on the service date
- All required fields present
- Address matches parcel 083-82-01001
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
5874 Ridgeview Rd
Owner: Jordan Hollins
Parcel 083-82-01001