Back to the backflow review queue

Backflow assembly test: 1383 Pine Knoll Ln

Approved

Filed Nov 16, 2026 by Reese Ashby, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 16, 2026
Assembly type
RP
Serial number
B829104
Size
1
Test gauge serial
G-1166
Gauge calibration date
Feb 24, 2026
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ashby, current on the service date
  • All required fields present
  • Address matches parcel 083-66-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1383 Pine Knoll Ln
Owner: Blake Kessler
Parcel 083-66-01279