Back to the backflow review queue

Backflow assembly test: 1281 Old Church Dr

Approved

Filed Oct 19, 2025 by Casey Hollins, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 19, 2025
Assembly type
RP
Serial number
W573730
Size
1
Test gauge serial
G-2150
Gauge calibration date
Feb 1, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Hollins, current on the service date
  • All required fields present
  • Address matches parcel 083-17-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1281 Old Church Dr
Owner: Riley Whitcomb
Parcel 083-17-01313