Backflow assembly test: 1281 Old Church Dr

Approved

Filed Nov 7, 2026 by Reese Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 7, 2026
Assembly type
RP
Serial number
W573730
Size
1
Test gauge serial
G-7047
Gauge calibration date
Mar 7, 2026
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Kessler, current on the service date
  • All required fields present
  • Address matches parcel 083-17-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.