Backflow assembly test: 6200 Hickory Ct

Approved

Filed Jun 18, 2024 by Jordan Fairley, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 18, 2024
Assembly type
RP
Serial number
W590771
Size
1
Test gauge serial
G-8203
Gauge calibration date
Mar 17, 2024
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Fairley, current on the service date
  • All required fields present
  • Address matches parcel 083-51-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6200 Hickory Ct
Owner: Blake Ashby
Parcel 083-51-01315