Backflow assembly test: 4059 Pine Knoll Ln

Approved

Filed Nov 9, 2026 by Hayden Whitcomb, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 9, 2026
Assembly type
PVB
Serial number
B570486
Size
1
Test gauge serial
G-7118
Gauge calibration date
Sep 5, 2026
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 085-27-01138
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.