Backflow assembly test: 3573 Spring Branch Ln

Approved

Filed Nov 30, 2024 by Reese Calloway, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 30, 2024
Assembly type
RP
Serial number
K951859
Size
3/4
Test gauge serial
G-9523
Gauge calibration date
Oct 26, 2024
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
3.7 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 085-54-01086
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3573 Spring Branch Ln
Owner: Riley Kessler
Parcel 085-54-01086