Backflow assembly test: Two Rivers Elementary School

Approved

Filed Jun 9, 2025 by Cameron Nguyen, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jun 9, 2025
Assembly type
RP
Serial number
A968021
Size
4
Test gauge serial
G-7292
Gauge calibration date
Feb 25, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-78-01025
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8358 Ridgeview Way
Owner: Kessler Holdings LLC
Parcel 085-78-01025