Back to the backflow review queue
Backflow assembly test: Main Street Animal Hospital
ApprovedFiled Mar 13, 2024 by Hayden Danner, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 13, 2024
- Assembly type
- RP
- Serial number
- Z235664
- Size
- 1
- Test gauge serial
- G-1161
- Gauge calibration date
- Aug 24, 2023
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 085-10-01312
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4085 Mill Creek Dr
Owner: Harlow Holdings LLC
Parcel 085-10-01312