Back to the backflow review queue

Backflow assembly test: Main Street Animal Hospital

Approved

Filed Mar 23, 2026 by Cameron Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 23, 2026
Assembly type
RP
Serial number
Z235664
Size
1
Test gauge serial
G-9175
Gauge calibration date
Jan 5, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-10-01312
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4085 Mill Creek Dr
Owner: Harlow Holdings LLC
Parcel 085-10-01312