Backflow assembly test: 2868 Cedar Hollow Ct

Approved

Filed Oct 20, 2024 by Reese Calloway, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Oct 20, 2024
Assembly type
RP
Serial number
B226563
Size
3/4
Test gauge serial
G-6807
Gauge calibration date
Dec 2, 2023
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
3.5 psid
Relief valve opened at
3.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 085-36-01305
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2868 Cedar Hollow Ct
Owner: Taylor Ellery
Parcel 085-36-01305