Back to the backflow review queue
Backflow assembly test: 7904 Stone Gate Way
ApprovedFiled Aug 22, 2025 by Hayden Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 22, 2025
- Assembly type
- RP
- Serial number
- A751082
- Size
- 3/4
- Test gauge serial
- G-4489
- Gauge calibration date
- Aug 30, 2024
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Whitcomb, current on the service date
- All required fields present
- Address matches parcel 085-17-01311
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7904 Stone Gate Way
Owner: Avery Marsh
Parcel 085-17-01311